GN30-12 12kV Rotary Indoor High-voltage Disconnect Switch

GN30-12 rotary indoor high-voltage disconnect switch is designed for 12kV indoor AC distribution systems.

It provides reliable no-load isolation, compact installation, and safe operation for switchgear and substations.

其他信息

Product Details:

The GN30-12 series indoor disconnect switch is a rotary-type isolating switch developed for indoor medium-voltage systems with rated voltage up to 12kV and frequency of 50/60Hz. It is mainly used for:

  • opening and closing no-load circuits,
  • providing visible isolation points,
  • ensuring maintenance safety,
  • grounding de-energized circuits (D type).

The switch can be installed:

  • independently,
  • inside high-voltage switchgear panels,
  • in RMU and distribution cabinets.

The GN30-12D version includes an additional grounding knife switch for enhanced operational safety.

Main Features

  • Rated voltage: 12kV
  • Rotary contact knife structure
  • Compact installation size
  • Strong insulation capability
  • Reliable visible isolation gap
  • Easy installation and adjustment
  • Optional grounding switch (GN30-12D)
  • Suitable for indoor switchgear systems
  • Stable mechanical and electrical performance

Technical Specifications

Item Specification
Rated Voltage 12kV
Maximum Voltage 12kV
Rated Frequency 50/60Hz
Rated Current 400A / 630A / 1000A / 1250A
Short-Time Withstand Current 12.5kA / 20kA / 31.5kA
Peak Withstand Current 31.5kA / 50kA / 80kA
Short-Circuit Duration 4s
Power Frequency Withstand Voltage 42kV
Lightning Impulse Withstand Voltage 75kV / 85kV
Mechanical Life ≥2000 operations
Installation Type Indoor

Model Meaning

Typical models include:

  • GN30-12/400-12.5
  • GN30-12/630-20
  • GN30-12/1000-31.5
  • GN30-12D/1250-31.5

Meaning:

  • GN = Indoor disconnect switch
  • 30 = Design serial number
  • 12 = Rated voltage (kV)
  • D = With grounding switch
  • 400 / 630 / 1000 / 1250 = Rated current (A)
  • 12.5 / 20 / 31.5 = Short-time withstand current (kA)

Working Conditions

  • Ambient temperature: -10°C to +40°C
  • Altitude: ≤1000m
  • Relative humidity:
    • Daily average ≤95%
    • Monthly average ≤90%
  • Earthquake intensity: ≤8 degree
  • Installation site should be free from:
    • explosive materials,
    • corrosive gases,
    • severe dust,
    • frequent violent vibration.

Applications

  • Medium-voltage switchgear
  • Indoor substations
  • Ring main units (RMU)
  • Transformer isolation systems
  • Industrial power distribution
  • Electrical maintenance isolation

Product Advantages

Compact Rotary Design

The rotary blade structure minimizes installation space and is suitable for compact switchgear cabinets.

Reliable Isolation

Provides a clear visible disconnection point for maintenance safety.

Strong Insulation Performance

Designed for stable operation in medium-voltage indoor systems.

Easy Maintenance

Simple mechanical structure allows convenient installation and long-term maintenance.

 

 

Outline Drawing

 

 

en_USEnglish

Ask For A Quick Quote

We will contact you within 1 working day, please pay attention to the email with the suffix “@wolunele.com”