ZW43(A)-12 11kV 12kV High Voltage Outdoor Vacuum Circuit Breaker

11kV 12kV High Voltage Outdoor Vacuum Circuit Breaker

Additional information

Product Details:

ZW43(A)-12 11kV 12kV High Voltage Outdoor Vacuum Circuit Breaker

 

General Introduction

ZW43-12 model outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit current in12kV, 50/60Hz power system. It is applicable for substations, industry and mining, urban and rural electricity power networks, especially applicable in occasions with frequent operation and automatic power distribution network. It accords with the standard of IEC62271-100 & GB1984: AC high voltage cir cuit breaker, IEC60694 & GB/T11022: HV general technical requirement of switch and control apparatus.

 

Working Condition

1. Altitude: 2000mm;

2. Ambient temperature: -40 ~+45 ;

3. Earthquake intensity: 8 degree;

4. Ice thickness: 10mm;

5. Wind speed: 34m/s (air pressure 700Pa)

 

Features

1. Mini vacuum arc extinguish High reliability; small volume; long life time; fixed inside the epoxide resin.

2. Epoxide resin sealing Anti-ozone, anti-ultraviolet; It is firm, light and convenience for transport.

3. Permanent magnet mechanism Small volume, reliable performance, non-maintenance.

4. Manual breaking Improve the reliability, It can operate under the urgent condition.

5. Direction tester It is mounted on the linkage axial to check the opening and closing direction.

6. Switch case Aluminium-alloy material, anti-rust steel and armor plate.

 

Technical Specification

No. Item Unit Data
1

2

3

4

5

6

7

8

9

10

11

12

13

14

Rated voltage

Rated frequency

Rated current

Rated short-circuit breaking current

Rated peak withstand current(peak)

4s rated short-time withstand current

Rated short-circuit making current (peak)

Mechanical duration

Breaking time of rated short-circuit breaking current

1min P.F withstand voltage-dry(phase to phase, to earth; across open contacts)

1min P.F withstand voltage-wet

Lightning impulse withstand voltage peak(phase to phase, to earth; across open contacts)

Net weight

Abrasions thickness of contacts

kV

Hz

A

kA

kA

kA

kA

Times

Times

kV

kV

kV

kg

mm

12

50/60

630

20

50

20

50

30000

30

42/49

34

75/85

70

3

Outline Drawing

 

 

 

Ask For A Quick Quote