XRNM1 SEKERING TEGANGAN TINGGI

Kategori
Specialized XRNM1 current-limiting fuse, dedicated to short-circuit and overload protection for 3.6kV-12kV medium-voltage motors, ensuring safe and stable operation of motor systems.

Informasi Tambahan

Detail Produk:

Product Overview

The XRNM1 series high voltage fuse is a professional current-limiting protective component specifically designed for medium-voltage motor protection in 3.6kV-12kV AC power systems (50Hz). It is mainly used for short-circuit and overload protection of medium-voltage motors, as well as protection of related auxiliary equipment in motor circuits. With its excellent current-limiting performance, high breaking capacity, and precise fusing characteristics, it can quickly cut off fault currents in milliseconds, effectively protecting motors from damage caused by short-circuit currents and overloads, and ensuring the safe and continuous operation of the entire motor drive system. It is widely applied in industrial and mining enterprises, chemical plants, power plants, and other scenarios with medium-voltage motor equipment.

 

Model & Makna

Sekring Tegangan Tinggi XRNM1

Spesifikasi Teknis

 

Model Nilai tegangan (KV) Nilai arus dari tautan sekring (A) Nilai arus putus (KA) Dimensi (mm) Gambar 1 Berat (Kg)
Asing Model Cina Gbr. ΦD L
WDF.O XRNM1 3.6 50, 63, 80, 100,125 50 Gambar 1 ~ 2 51 254 1.4
WFF.O XRNM1 3.6 100, 125, 160, 200 50 76 254 2.8
WKF.O XRNM1 3.6 250, 315, 355, 400 50 76 254 2.8
WFN.O XRNM1 7.2 25, 31.5, 40, 50, 63, 80, 100, 125, 160 40 76 403 4.15
WKN.O XRNM1 7.2 200, 224 40 76 403 4.15
XRNM1 10 25, 31.5, 40, 50, 63, 80, 100, 125, 160, 200, 224 40 76 600 5.26

Catatan:

  • Dalam kondisi yang ditentukan, arus putus sekering bisa mencapai 2,5 ~ 3,0 kali lipat dari arus pengenal.
  • Tautan sekering 7.2KV 224A atau lebih tinggi memiliki bodi tabung ganda
  • Tautan sekering 3,6KV 400A atau lebih tinggi memiliki bodi tabung ganda

Core Features

  • Professional Motor Protection Design: Specifically developed for medium-voltage motor circuits, it can withstand the 7-10 times rated current starting impact of motors without misoperation, while providing reliable protection against short-circuit and overload faults.
  • High Breaking Capacity: Adopts advanced current-limiting structure with a rated breaking capacity of 40kA-50kA, which can quickly limit fault currents to a safe range before the peak value, minimizing the impact of short-circuit currents on motors and power grids.
  • Low Arc Voltage & High Safety: The arc voltage generated during breaking is low, and it will not damage the insulation of the system. It can be used in systems lower than the rated voltage (e.g., 12kV fuses for 7.2kV systems) with high safety.
  • Durable Ceramic Structure: The outer tube is made of high-strength alumina ceramic, which has excellent high-temperature resistance, pressure resistance, and insulation performance. It can withstand the high temperature and pressure generated during arc extinction, ensuring long service life.
  • Easy Installation & Wide Compatibility: Designed for indoor cabinet installation, with compact structure and standardized size, suitable for most medium-voltage switchgears and motor control cabinets. Factory-calibrated, no additional adjustment is required during installation.

Garis Besar & Gambar

 

 

id_IDIndonesian

Minta Penawaran Cepat

Kami akan menghubungi Anda dalam waktu 1 hari kerja, harap perhatikan email dengan akhiran "@wolunele.com"