| Maximum continuous permissible operating voltage, value, kV |
24 * ) |
| Rated voltage, kV, not less |
thirty |
| Classification voltage at classification current 2 mA, kV, not less |
thirty |
| Throughput current on a rectangular pulse with a duration of 2000 μs, A |
400 |
550 |
650 |
| Rated discharge current, kA |
10 |
| The remaining voltage at the arrester with a current pulse of 30/60 μs with an amplitude: |
|
| – 250 A, kV, no more |
59.6 |
| – 500 A, kV, no more |
62.7 |
| – 1000 A, kV, no more |
65.9 |
| Remaining voltage at the surge arrester with a current pulse of 8/20 µs with amplitude: |
|
| – 5000 A, kV, no more |
72.1 |
| – 10000 A, kV, no more |
78.5 |
| – 20000 A, kV, no more |
84.0 |
| Remaining voltage at the arrester at a pulse of 1/4 μs with the amplitude of the rated discharge current, kV, no more |
91.2 |
| High current pulse amplitude 4/10 μs, kA |
65 |
100 |
| Specific dissipated energy, over two pulses, kJ/kV, not less |
4.2 |
6.4 |
7.8 |
| Leakage distance of external insulation, cm/kV, |
at customer’s request
2.25, 2.5 and 3.1 |
| Electrical strength of external insulation |
according to GOST R 52725 |
| Explosion-proof current according to GOST R 52725 |
40 kA |
| Warranty period, years |
|
| for surge arresters |
1 |
| for MOPN1 |
|
| Estimated service life, years |
|
| for surge arresters |
thirty |
| for MOPN |
40 |
| Guaranteed shelf life in manufacturer’s containers, years |
1 |