RN2 High Voltage Fuse for Generator PT

分类

RN2 potential transformer fuse

Thông tin bổ sung

Product Details:

General Description

RN2 series indoor high voltage current limiting fuse is a professional protection component specially developed for Potential Transformer (PT) and generator loop protection in medium voltage power systems. It is widely applied in indoor high voltage switchgear, power distribution substations, industrial power plants, and generator control rooms, serving as reliable short-circuit and overload protection for voltage transformers and related high voltage auxiliary circuits.

This fuse adopts high-strength ceramic outer tube, filled with high-purity quartz sand as arc-extinguishing medium, matched with precision melt inside. Under normal operating conditions, the fuse keeps stable conducting state with low power loss. When the circuit suffers short-circuit fault or abnormal overcurrent, the melt fuses instantly, and the quartz sand quickly absorbs arc energy to realize rapid arc extinction and current limiting, effectively isolating the faulty circuit and protecting PT equipment and the whole power system from damage.
Mainly designed for indoor working environment, RN2 high voltage fuse supports multiple rated voltage levels including 3kV, 6kV, 10kV, 15kV, 20kV and 35kV. The standard rated current for PT protection is 0.5A, which perfectly matches the no-load and light-load working characteristics of potential transformers. It features accurate fusing characteristic, low overvoltage impact during breaking, high breaking capacity and stable electrical performance under long-term continuous operation.

With compact integrated structure, rigorous manufacturing process and good mechanical vibration resistance, the RN2 fuse is easy to install, replace and maintain. It complies with IEC 60282 and GB/T 15166.2 international and national standards, ensuring safe and reliable operation in various complex medium voltage power distribution occasions. It is the ideal dedicated protective fuse for generator PT, indoor high voltage cabinet, substation PT loop and industrial high voltage power distribution system.

Technical Data

Model RN2-3, 6, 10 RN2-15, 20 RN2-35
Rated Voltage 3 6 10 15 20 35
Rated Current 0.5 0.5 0.5
Three-phase Breaking Capacity 1000
Max. Breaking Current(Effective value) 100 85 50 40 30 17
Max. peak current at max. breaking short circuit current 160 300 1000 350 850 700
Overvoltage Not more than 2.5 times of operating voltage
Resistance of Melt Pipe 100±7 200±10 380±10
Weight 5.6 12 15.6
Weight of Melt Pipe 0.9 1.6 2.5

 

Key Specifications

  • Model: RN2
  • Rated Voltage: 3kV / 6kV / 10kV / 15kV / 20kV / 35kV
  • Rated Current: 0.5A (standard for PT protection)
  • Rated Frequency: 50Hz / 60Hz
  • Breaking Capacity (Three-phase): Up to 1000 MVA
  • Max Breaking Current (rms):
    • 3kV: 100kA
    • 6kV: 85kA
    • 10kV: 50kA
    • 15kV: 40kA
    • 20kV: 30kA
    • 35kV: 17kA
  • Fusing Characteristic: 0.6–1.8A fusing current within 1 minute
  • Overvoltage Limitation: ≤2.5× rated voltage
  • Installation: Indoor, for PT primary side protection
  • Material: Ceramic tube with quartz sand filler
  • Standard: IEC 60282, GB/T 15166.2

Main Features

• ✅ PT & Generator Dedicated: Specifically for potential transformer (PT) and generator protection
• ✅ Current Limiting: Fast-acting, limits short-circuit current before peak
• ✅ High Reliability: Stable performance in indoor MV switchgear
• ✅ Compact & Easy Mounting: Simple structure, easy installation and replacement

Applications

• Generator voltage transformers (PT)
• Indoor MV switchgear (3–35kV)
• Power distribution substations
• Industrial plant PT circuits

Outline Dimensions 

Outline Dimensions of Model RN2-3, 6, 10/0.5

rn2 fuse dimension 1

 

Outline Dimensions of Model RN2-15, 20/2-0.5

rn2 fuse dimension 2

Outline Dimensions of Model RN2-35/0.5

rn2 fuse dimension 3

viVietnamese

Ask For A Quick Quote

We will contact you within 1 working day, please pay attention to the email with the suffix “@wolunele.com”