Y10W Power Substation Type Polymer Lightning Arrester

Power Substation Type Polymer Lightning Arrester

Additional information

Product Details:

Power Substation Type Polymer Lightning Arrester

 

General Introduction

Wolun Polymer Lightning Arresters are manufactured to offer optimum protection to distribution equipment such as transformers and similar assets against the damaging lightning effects and similar operational conditions. These arresters perform their task with high-end improvement and fidelity towards surge switching and medium voltage networks. Maintenance of service safety for both underground and overheard setups is offered without any trouble on exposure in the outdoors for long durations. Going through precision tests have made Wolun arresters more durable & reliable.

 

Working Conditons

1. The ambient air temperature is no higher than +40°C, no lower than -40 °C .

2. The altitude above sea level does not exceed 1000m. ( the plateau area should be indicated when order.)

3. AC system frequency is 50Hz or 60Hz.

4. Power frequency voltage brought to bear on arrester for a long time does not exceed the continuous operation voltage of the arrester.

5. Maximum wind speed does not exceed 35m/s.

6. Te earthquake intensity does not exceed 7 degrees.

7. The pollution area should be indicated.

 

Features

  • It adopts double sealing structure, the core encapsulates by molded silicone rubber which completely solves the sealing problem of porcelain housed products.
  • It has a two-way pressure release structure.
  • Its core component ZnO varistor has good pressure ratio, consistency, large flow capacity and high reliability.
  • E creepage distance of porcelain housed products is wide which is suitable for IV level heavy pollution areas.

 

Technical Specification

 

Type Nominal System Voltage Rated Voltage Continuous Operating Voltage MRV under 1/5 μ s Steeo Discharge Current MRV under 8/20 μ s Lightning Discharge Current MRV under 30/60 μ s Operating Discharge Current Minmum Reference Voltage under 1 mA DC 4/10 μ s High Current Impulse Twice (KA) 2mS

SW through-flow capacity A/18

Line Discharge Class
10KA 20KA 5KA 10KA 0.5KA 1KA
Y10W5-102/266 123 102 81 277 235 258 203 210 148 100 850 3
Y10W5-108/281 145 108 86 295 249 274 215 222 157 100 850 3
Y10W5-111/290 145 111 88 303 257 282 222 229 161 100 850 3
Y10W5-120/313 145 120 98 327 277 304 239 247 174 100 850 3
Y10W5-126/329 145 126 100 344 291 320 251 259 183 100 850 3
Y10W5-132/344 145 132 106 359 305 334 263 272 192 100 850 3
Type Nominal System Voltage Rated Voltage Continuous Operating Voltage MRV under 1/5 μ s Steeo Discharge Current MRV under 8/20 μ s Lightning Discharge Current MRV under 30/60 μ s Operating Discharge Current Minmum Reference Voltage under 1 mA DC 4/10 μ s High Current Impulse Twice (KA) 2mS SW through-flow capacity A/18 Line Discharge Class
5KA 10KA 5KA 10KA 0.25KA 0.5KA
Y10W5-192/500 220 192 150 560 500 426 280 100 800 3
Y10W5-200/520 220 200 156 582 520 442 290 100 800 3
Y10W5-204/532 220 204 159 594 532 452 296 100 800 3
Y10W5-216/562 220 216 168.5 630 562 478 314 100 800 3

 

Type Nominal System Voltage Rated Voltage Continuous Operating Voltage MRV under 1/5 μ s Steeo Discharge Current MRV under 8/20 μ s Lightning Discharge Current MRV under 30/60 μ s Operating Discharge Current Minmum Reference Voltage under 1 mA DC 4/10 μ s High Current Impulse Twice (KA) 2mS SW through-flow capacity A/18 Line Discharge Class
10KA 20KA 10KA 20KA 0.5KA 2KA
Y10W5-420/960 500 420 318 1075 960 852 565 100 1500 4
Y20W5-420/1046 500 420 318 1070 1046 858 565 100 2000 5
Y10W5-444/1015 500 444 324 1137 1015 900 597 100 1500 4
Y20W5-444/1106 500 444 324 1238 1106 907 597 100 2000 5
Y10W5-468/1070 500 468 330 1198 1070 950 630 100 1500 4
Y20W5-468/1166 500 468 330 1306 1166 956 630 100 2000 5

 

 