11kV 12kV 24kV 27kV 33kV 36kV High Voltage Polymer Fuse Cutout

High Voltage Polymer Fuse Cutout

Additional information

voltage

12kV, 24kV, 36kV

Product Details:

11kV 12kV 24kV 27kV 33kV 36kV High Voltage Polymer Fuse Cutout 

 

Application

 

Polymer fuse cutouts are designed to provide protection to the lines of your systems and distribution transformer against overload and short circuit damage.

Ratings

We are able to offer several frame sizes to properly match each system BIL. Each fuse cutout support has universal contacts that accommodate a 100A or a 200A fuse holder.

Interchangeability

Our polymer cutout are designed to be electrically and mechanically interchangeable with the S&C Type “XS”, A.B. Chance type “C”, ABB type “ICX” and cooper type “L” cutouts, as well as all other fuse cutouts produced in accordance with the IEC282, IEEE C37.41 and C37.42 standards.

Efficient Current Transfer

Our polymer fuse cutout has an copper current path and all contacts are silver plated. Terminals are tin plated brass alloy for use with copper or aluminum conductors.

Polymer Insulator

Our fuse cutout insulators are manufactured from HTV silicone rubber with creepage distance range from 360mm-960mm with different BIL.

Higher interrupt capacities

By using a copper arc-shortening rod attached to the dome nut inside the top of the fuse tube, lowering the fuse link, higher interrupt ratings are obtainable. It is necessary to use fuse links with removable button heads when using an arc-shortening rod.

 

Technical Specification

10kV-15kV
Type Rated voltage kv Rated current A Breaking current A Impulse voltage bil A Power-frequency withstand voltage kv Creepage distance mm Weight
HRW12-12 12 100 10000 110 50 440 3.5
HRW12-12 12 200 12000 110 50 440 3.5
24kV-27kV
Type Rated voltage kv Rated current A Breaking current A Impulse voltage bil A Power-frequency withstand voltage kv Creepage distance mm Weight
HRW12-24 24 100 10000 150 70 600 4.6
HRW12-24 24 100 12000 150 70 600 4.9
33kV-36kV
Type Rated voltage kv Rated current A Breaking current A Impulse voltage bil A Power-frequency withstand voltage kv Creepage distance mm Weight
HRW12-36 36 100 10000 200 95 790 5.8
HRW12-36 36 200 12000 200 95 790 5.8

24kv 27kv FCO LBFCO

 

Ask For A Quick Quote

We will contact you within 1 working day, please pay attention to the email with the suffix “@wolunele.com”