LZZBJ9-24-180b/2 and LZZBJ9-24-180b/4 are indoor epoxy resin cast current transformers designed for 24kV medium voltage power systems.
They are widely used for current measurement, electric energy metering and relay protection in indoor switchgear and substations, featuring high insulation performance, compact structure and reliable operation
LZZBJ9-24-180b/2 and LZZBJ9-24-180b/4 are indoor epoxy resin cast current transformers designed for 24kV medium voltage power systems. These current transformers are widely used for current measurement, electric energy metering and relay protection in indoor switchgear, substations and power distribution systems.
The transformers adopt high-quality epoxy resin vacuum casting insulation with excellent dielectric strength, compact structure, stable performance and long service life. They are suitable for frequency 50Hz/60Hz AC systems with rated voltage up to 24kV.
– Rated insulation level: 24/65/125kV
– Rated secondary current: 5A or 1A
– Power frequency withstand voltage: 17.5kV, 24kV
– Rated frequency: 50/60Hz
– Ambient temperature: -5°C ~+40°C
– Altitude : ≤1000m
-Standard: IEC 60044-1, GB1208-200
| Rated transformer
Ratio(A) |
Secondary accuracy classes combination | Rated output
(VA) |
Measuring current’s instrument security factor | Protective current’s accuracy limit factor | Rated short-time thermal current (kA/S) | Rated dynamic current ( kA) | ||
| Measuring | Protective | |||||||
| 0.2(S) | 0.5 | 10P | ||||||
| 20-200/5 | 0.2(S)/0.2(S)
0.2(S)/0.5 0.2(S)/10P 0.5/10P |
10
15 |
15 | 15 | 5
(10) |
10
15 |
150I1n | 375I1n |
| 300/5 | 31.5 | 80 | ||||||
| 400/5 | 31.5 | 80 | ||||||
| 500/5 | 40 | 100 | ||||||
| 600/5 | 50 | 125 | ||||||
| 800/5 | 20 | 63 | 125 | |||||
| 1000/5 | 80 | 160 | ||||||
| 1250/5 | 80 | 160 | ||||||
| Rated transformer
Ratio(A) |
Secondary accuracy classes combination | Rated output
(VA) |
FS | ALF | Rated short-time thermal current (kA/S) | Rated dynamic current ( kA) | ||
| Measuring | Protective | |||||||
| 0.2(S) | 0.5 | 10P | ||||||
| 15-30/5
20-40/5 ………. 500-1000/5 |
0.2S/0.5/10P
0.2/0.5/10P 0.5/0.5/10P 0.2S/10P/10P 0.2/10P/10P 0.5/10P/10P |
15 | 15 | 10
15 |
5
(10) |
10
15 20 |
100I1n | 250I1n |
| 600-1200/5 | 50 | 105 | ||||||
| 750-1500/5 | 63 | 130 | ||||||
| 800-1600/5 | 80 | 160 | ||||||
| 1000-2000/5 | 80 | 160 | ||||||
| 1250-2500/5 | 100 | 200 | ||||||
| Rated transformer
Ratio(A) |
Secondary accuracy classes combination | Rated output
(VA) |
FS | ALF | Rated short-time thermal current (kA/S) | Rated dynamic current ( kA) | ||
| Measuring | Protective | |||||||
| 0.2(S) | 0.5 | 10P | ||||||
| 15-300/5 | 0.2S/0.5/10P
0.2/0.5/10P 0.5/0.5/10P 0.2S/10P/10P 0.2/10P/10P 0.5/10P/10P |
15 | 15 | 15
20 |
5
(10) |
10
15 20 |
100I1n | 250I1n |
| 400/5 ~600/5 | 50 | 105 | ||||||
| 800-1000/5 | 63 | 130 | ||||||
| 1200/5 | 80 | 160 | ||||||
| 1500/5 | 80 | 160 | ||||||
| 2000/5 | 100 | 200 | ||||||
| 2500/5 | 125 | 200 | ||||||





We will contact you within 1 working day, please pay attention to the email with the suffix “@wolunele.com”.