Chave de desconexão de alta tensão externa GW4 33kV 40.5kV

GW4 33kV / 40.5kV outdoor high voltage disconnect switch is designed for substation and transmission systems.

It provides reliable no-load isolation, visible disconnection, and safe outdoor operation for medium-voltage networks.

Informação adicional

Detalhes do produto:

The GW4 series covers voltage levels from 33kV, 35kV, to 40.5kV, making it widely used in 110kV and 66kV substations (step-down side applications) and medium-voltage distribution networks.

It is mainly used to:

  • isolate high-voltage equipment during maintenance
  • provide a visible air-gap disconnection point
  • safely disconnect busbars, transformers, and circuit breakers
  • operate only under no-load conditions

The switch is typically installed in:

  • outdoor substations
  • power plants
  • industrial switchyards
  • renewable energy (wind/solar) substations

Main Features

  • Rated voltage: 33kV / 40.5kV
  • Outdoor installation, heavy-duty design
  • Double-column or center-break structure
  • Visible isolation gap for safety confirmation
  • Manual or motorized operation available
  • Optional single or double grounding switch (D type)
  • Anti-pollution porcelain or composite insulators
  • Strong mechanical linkage system
  • Suitable for harsh outdoor environments

Technical Specifications (Typical for 40.5kV class)

Item Especificação
Tensão nominal 33kV / 40.5kV
Frequency 50/60Hz
Corrente nominal 630A / 1250A / 1600A / 2000A
Short-Time Withstand Current 20kA / 25kA / 31.5kA / 40kA
Peak Withstand Current 50kA / 63kA / 80kA / 100kA
Power Frequency Withstand Voltage ~95kV
Lightning Impulse Withstand Voltage ~185kV
Mechanical Life ≥2000 operations
Installation Type Outdoor

Significado do modelo

Typical model examples:

  • GW4-33
  • GW4-40.5
  • GW4-40.5D (with grounding switch)
  • GW4-40.5W (anti-pollution type)

Meaning:

  • GW = Outdoor disconnect switch
  • 4 = Design series
  • 33 / 40.5 = Rated voltage (kV)
  • D = With grounding knife switch
  • W = Anti-pollution version
  • 630 / 1250 = Rated current

Condições de trabalho

  • Temperatura ambiente: -30°C to +40°C
  • Altitude: ≤3000m
  • Wind speed: ≤35m/s
  • Pollution level: Class III
  • Intensidade do terremoto: ≤8 graus
  • No flammable, explosive, or corrosive environment

Aplicativos

  • Outdoor substations (33kV / 40.5kV systems)
  • Power transmission & distribution networks
  • Transformer isolation switching
  • Circuit breaker maintenance isolation
  • Solar and wind power substations
  • Industrial power systems

Product Advantages

High Safety Isolation

Provides a clear visible break, ensuring safe maintenance operations.

Strong Outdoor Durability

Designed for long-term exposure to UV, rain, wind, and pollution.

Flexible Configuration

Supports grounding switches, motor operation, and anti-pollution upgrades.

Reliable Mechanical Structure

Robust linkage ensures synchronized phase operation and long service life.

Desenho de contorno

 

 

 

pt_BRPortuguese

Solicite uma cotação rápida

Entraremos em contato com você dentro de 1 dia útil, preste atenção ao e-mail com o sufixo "@wolunele.com"