ZN12-12(40.5) is a 12kV/40.5kV indoor AC high voltage vacuum circuit breaker with vacuum arc extinguishing structure. Featuring reliable breaking performance, long service life and low maintenance, it is widely used in power plants, substations and industrial high-voltage distribution systems.
The ZN12-12(40.5) is a three-phase AC 50Hz indoor high-voltage vacuum circuit breaker, covering two voltage levels: 12kV and 40.5kV.
It adopts advanced vacuum arc-extinguishing technology, which has the advantages of strong breaking capacity, long electrical and mechanical life, and no environmental pollution.
It is mainly used for control and protection of power transmission and distribution equipment in power plants, substations, industrial and mining enterprises, and other places, and is especially suitable for occasions requiring frequent operation.
1. الارتفاع 1000m;
2. درجة الحرارة المحيطة: -25 ~ +40;
3. الرطوبة النسبية: المتوسط اليومي 95، المتوسط الشهري 90;
4. شدة الزلزال: 8 درجات;
5. يجب أن تكون المناسبات القابلة للتطبيق خالية من المواد القابلة للاشتعال والمتفجرات والمواد المسببة للتآكل والاهتزازات الشديدة.
1. قدرة الكسر لغرفة إطفاء القوس الكهربائي عالية، والقدرة الاستيعابية الحالية منخفضة، والعمر الكهربائي طويل.
2. التصميم من الأمام إلى الخلف، هيكل بسيط ومضغوط، تشغيل كامل وصيانة سهلة.
3. من أجل الهيكل والتركيب، يمكن تقسيمها إلى: نوع ثابت أفقي، نوع ثابت مائل، نوع ثابت مائل، نوع متحرك متوسط المجموعة الوسطى.
|
اسم المعلمة
|
Specification (12kV)
|
Specification (40.5kV)
|
|---|---|---|
|
الفولتية المقدرة
|
12 كيلو فولت
|
40.5kV
|
|
التردد المقدر
|
50Hz
|
50Hz
|
|
التيار المقنن
|
630A, 1250A, 1600A, 2000A
|
630A, 1250A, 1600A, 2000A
|
|
Rated Short-Circuit Breaking Current
|
20kA, 25kA, 31.5kA, 40kA
|
20kA, 25kA, 31.5kA, 40kA
|
|
1min Power Frequency Withstand Voltage
|
42kV
|
95kV
|
|
Lightning Impulse Withstand Voltage (Peak)
|
75kV
|
185kV
|
|
Operating Mechanism
|
Spring Energy Storage Type (AC/DC Dual-Use, Manual Optional)
|
Spring Energy Storage Type (AC/DC Dual-Use, Manual Optional)
|
|
Mechanical Life
|
≥10,000 Times
|
≥10,000 Times
|
| ق/م | البند | الوحدة | البيانات | ||||
|---|---|---|---|---|---|---|---|
| 1 | تقييمه
الفولطية |
كيلو فولت | 12 | ||||
| 2 | مستوى العزل المقدر | 1 دقيقة طاقة
التردد الصمود الفولطية |
42 | ||||
| البرق
الاندفاع الصمود الفولطية |
75 | ||||||
| 3 | التردد المقدر | هرتز | 50 | ||||
| 4 | التيار المقنن | A | 6301250
1600 |
12501600
2000 2500 3150 |
12501600
2000 2500 3150 |
20002500
3150 4000 |
|
| 5 | تيار قطع الدائرة القصيرة المقدر | ك أ | 20/25 | 31.5 | 40 | 50 | |
| 6 | 4 ثوانٍ من الوقت القصير لتحمل التيار | 20/25 | 31.5 | 40/3s | 50/3s | ||
| 7 | تيار صنع الدائرة القصيرة المقدر (الذروة) | 50/63 | 80 | 100 | 125 | ||
| 8 | تيار التحمل الأقصى المقدر (الذروة) | 50/63 | 80 | 100 | 125 | ||
| 9 | أزمنة كسر تيار كسر الدائرة القصيرة المقدرة | الأوقات | 50 | 30 | |||
| 10 | الحياة الميكانيكية | 10000 | 6000 | ||||
| 11 | وقت الإغلاق | ms | ≤75 | ||||
| 12 | وقت الافتتاح | ≤65 | |||||
| 13 | مسافة مركز الطور | مم | 210、230、250、275 | ||||